Electrical installations in patient areas and Body Protected Areas

 

AS/NZS 3003:2018 provides specific electrical safety requirements for patient areas in healthcare facilities.

 

It is one of the key standards used by ClinicCheck, the medical equipment testing and compliance division of NZ Test Group.

 

The standard addresses electrical installations in patient areas, including Body Protected Areas (BPAs), electrical protection, identification, inspection and testing.

​

What Does AS/NZS 3003 Cover?

 

AS/NZS 3003 applies to electrical installations in areas where certain medical electrical equipment is intended to be used on patients.

 

These requirements are additional to the general electrical installation requirements of AS/NZS 3000.

 

The standard provides guidance on patient area classification, electrical protection, socket-outlets, RCDs, signage, inspection and testing.

 

What Is a Body Protected Area?

 

A Body Protected Area (BPA) is a patient area designed to provide additional electrical protection where medical electrical equipment is used on patients.

 

These areas commonly occur in medical practices, treatment rooms, hospitals and other healthcare facilities.

 

The electrical installation must provide appropriate protection to reduce the risk of electric shock to patients and healthcare personnel.

 

Does Every Medical Consultation Room Need to Be a BPA?

 

No.  Not every consultation room automatically requires Body Protected Area classification.

 

The classification depends on the medical procedures undertaken and the electrical equipment used on patients.

 

For example, a consultation room used primarily for discussions and routine examinations may not require BPA classification.

 

However, a treatment room where mains-powered medical electrical equipment is applied to patients may require additional electrical protection.

​

The intended clinical use of the room is an important factor in determining its classification.

 

What About RCD Protection?

 

Residual Current Devices (RCDs) are an important part of electrical safety in patient areas.

 

Body Protected Areas generally require additional protection through appropriately installed 10 mA RCDs.

 

AS/NZS 3003 also addresses the location, accessibility, identification and testing of electrical protection devices.

 

The requirements differ from those applying to ordinary workplace electrical installations.

 

Do Existing Patient Areas Built to AS/NZS 3003:2011 Need Upgrading?

Not automatically.

 

An existing patient area that was correctly installed and complied with AS/NZS 3003:2011 (or an earlier applicable version) does not necessarily need to be upgraded simply because AS/NZS 3003:2018 has subsequently been adopted.

 

Existing installations can generally continue operating under the requirements applicable when they were installed, provided they remain electrically safe and suitable for their intended use.

 

However, alterations, additions or repairs to an existing patient area can trigger requirements under AS/NZS 3003:2018.

 

Depending on the nature of the work and the existing installation, this may require upgrading the affected area to meet the current standard.

​

 

This is particularly important when renovating treatment rooms, installing additional socket-outlets or changing how a room is used.

 

A room's original compliance does not automatically establish compliance for new electrical work.

 

What Must Happen Before Major Alterations Are Carried Out?

 

Before alterations or additions are undertaken in an existing Body Protected Area, the electrical installation must have been inspected and tested within the preceding 12 months.

 

If the required inspection and testing have not been completed within that period, the area must be assessed before the proposed work proceeds.

​

The electrician undertaking the work must also consider the requirements of AS/NZS 3003:2018 and determine what changes are necessary.

​

This helps ensure that alterations do not compromise the existing electrical protection provided to patients.

 

How Often Must Body Protected Areas Be Tested?

​

AS/NZS 3003:2018 provides for routine inspection and testing of patient areas.

​

For Body Protected Areas, this generally involves inspection and testing at intervals not exceeding 12 months.

 

Testing helps verify that the electrical protection arrangements continue to operate as intended.

 

Appropriate records should be maintained, including inspection dates, test results and any identified defects.

 

What About BPA Signage?

 

Body Protected Areas require appropriate identification.

 

Signage helps healthcare personnel and electrical workers recognise that the room has specific electrical protection requirements.

 

The identification also provides information relating to the inspection and testing of the patient area.

 

Correct signage is an important part of maintaining an identifiable and appropriately managed patient area.

 

Who Is Responsible for Identifying Patient Areas?

 

The healthcare provider or organisation responsible for the facility plays an important role in determining how rooms are used.

 

This includes identifying the medical procedures undertaken and the equipment intended to be used on patients.

 

The classification of patient areas should be established in consultation with appropriately qualified electrical and healthcare professionals.

 

Changes to clinical procedures or equipment may require the classification to be reviewed.

 

Where Does AS/NZS 3003 Fit With Other Standards?

 

AS/NZS 3003 addresses the electrical installation within patient areas.

 

AS/NZS 3551 provides a framework for the management, testing and verification of medical electrical equipment.

 

AS/NZS 3760 is commonly used for the inspection and testing of ordinary in-service electrical equipment.

 

These standards can operate alongside one another within healthcare facilities.

 

Understanding which standard applies to the equipment and which applies to the electrical installation is essential.

 

Need Help With AS/NZS 3003?

​

ClinicCheck – Medical Equipment Testing & Compliance

​

ClinicCheck provides medical equipment testing, verification and compliance solutions as part of NZ Test Group.

 

If you're unsure whether your treatment rooms require BPA classification, inspection or testing, talk to our team.

​